6.11 Communication via EtherNet/IP
6.11.5
Integrate the drive device into the Ethernet network via DHCP
Integrating the drive into the EtherNet/IP network via the onboard PROFINET interface X150.
Proceed as follows to integrate the drive into EtherNet/IP:
1. Set p8924 (PN DHCP mode) = 2 or 3
2. Save the settings with p8925 = 2.
The next time that it is run-up, the drive retrieves the IP address made available by a
DHCP server. After the drive has run-up, you can address the drive as Ethernet
participant.
Note
Immediate switchover without restart
The switchover to DHCP is performed immediately and without a restart if the change is
carried out with the EIP command "Set Attribute Single" (class F5 hex, attribute 3), e.g.
using:
• An EIP control
• An EIP commissioning tool
Displays:
● r8930: Station name of the onboard PROFINET interface X150
● r8934: DHCP mode of the onboard PROFINET interface X150
● r8935: MAC address of the onboard PROFINET interface X150
414
Parameterization
Meaning
p8924 = 2
The DHCP server assigns the IP address based on the MAC address.
p8924 = 3
The DHCP server assigns the IP address based on the station name.
Operating Instructions, 12/2018, A5E36652151A