Error
Meaning
value
0x6B
Write access for the enabled
controller.
0x6C
Parameter %s [%s]: Unit unknown.
0x6D
Parameter %s [%s]: Write access
only in the commissioning state,
encoder (p0010 = 4).
0x6E
Parameter %s [%s]: Write access
only in the commissioning state,
motor (p0010 = 3).
0x6F
Parameter %s [%s]: Write access
only in the commissioning state,
power unit (p0010 = 2).
0x70
Parameter %s [%s]: Write access
only in quick commissioning
(p0010 = 1).
0x71
Parameter %s [%s]: Write access
only in the ready state (p0010 = 0).
0x72
Parameter %s [%s]: Write access
only in the commissioning state,
parameter reset (p0010 = 30).
0x73
Parameter %s [%s]: Write access
only in the commissioning state,
safety (p0010 = 95).
0x74
Parameter %s [%s]: Write access
only in the commissioning state, tech.
application/units (p0010 = 5).
0x75
Parameter %s [%s]: Write access
only in the commissioning state
(p0010 not equal to 0).
0x76
Parameter %s [%s]: Write access
only in the commissioning state,
download (p0010 = 29).
0x77
Parameter %s [%s] must not be
written during download.
0x78
Parameter %s [%s]: Write access
only in the commissioning state, drive
configuration (device: p0009 = 3).
0x79
Parameter %s [%s]: Write access
only in the commissioning state,
define drive type (device: p0009 = 2).
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
6.7 Communication according to PROFIdrive
Comment
Write access is possible while the device is in the
"Controller enable" state.
Pay attention to the parameter attribute "changeable" in
the List Manual (C1, C2, U, T).
Operation
Additional
info
333