Data Transfer; Access Rights - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Functions, monitoring and protective functions
9.3 Drive functions

Data transfer

Access is performed by unsecured (http) or secured transmission (https).
The type of transmission is defined by entering the corresponding address.
For safety reasons, secure transmission can be forced by deactivation of the http port.
Access
The web server is accessed via the following interfaces:
● LAN interface X127 of the Control Unit CU320-2 DP or CU320-2 PN
● PROFINET interface X150 of the CU320-2 PN
The drive is addressed using the IP address.
The IP address can be taken from the following parameters:
● Integrated Ethernet interface (LAN interface): r8911[0...3]
The service interface has the following default setting:
– IP address: 169.254.11.22
– Subnet mask: 255.255.0.0
● PROFINET interface: r8931[0...3]
Note
The IP addresses of the service and PROFINET interfaces must not be in the same subnet.

Access rights

● Administrator
● SINAMICS
580
Access
The "Administrator" user has full access to the converter data displayed in the web
rights
server.
Password
To access the converter, an administrator password must be assigned.
Access
The "SINAMICS" user has restricted access rights in the default settings of the web
rights
server.
Password
By default, a password is not assigned for the "SINAMICS" user.
Operating Instructions, 12/2018, A5E36652151A