Advertisement

Commissioning
5.3 Procedure for commissioning with STARTER
NOTICE
Erroneous temperature evaluation due to incorrectly selected article numbers of the
installed Active Interface Module
Since 2016, a PT1000 temperature sensor has been used for recording the temperature of
the line reactor of the Active Interface Module.
An incorrectly selected line filter (Active Interface Module) leads to an erroneous default
setting of the temperature sensor and thus to an erroneous temperature evaluation of the
installed filter reactor. It can also lead to fault messages or warning messages.
• Select the correct article number of the selected line filter (Active Interface Module).
⇒ Click Next >
Selecting the control structure
Figure 5-16
216
Selecting the control structure
Operating Instructions, 12/2018, A5E36652151A