Siemens SINAMICS S150 NEMA Operating Instructions Manual page 334

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Operation
6.7 Communication according to PROFIdrive
Error values in parameter responses
Table 6- 21
Error values in parameter responses
Error
Meaning
value
0x00
Illegal parameter number.
0x01
Parameter value cannot be changed.
0x02
Lower or upper value limit exceeded.
0x03
Invalid subindex.
0x04
No array.
0x05
Wrong data type.
0x06
Illegal set operation (only reset
allowed)
0x07
Description element cannot be
changed
0x09
No description data available
0x10
Read job will not be executed.
0x0B
No parameter change rights.
0x0F
No text array exists
0x11
Request cannot be executed due to
operating status.
0x14
Illegal value.
0x15
Response too long.
0x16
Illegal parameter address.
0x17
Illegal format.
0x18
Number of values inconsistent.
0x19
Drive object does not exist.
0x20
Parameter text cannot be changed.
0x21
Service is not supported.
0x65
Parameter presently deactivated.
332
Comment
Access to a parameter that does not exist.
Modification access to a parameter value that cannot be
changed.
Modification access with value outside value limits.
Access to a subindex that does not exist.
Access with subindex to an unindexed parameter.
Modification access with a value that does not match the
data type of the parameter.
Modification access with a value not equal to 0 in a case
where this is not allowed.
Modification access to a description element that cannot
be changed.
Access to a description that does not exist (the parameter
value exists).
The read request is refused because know-how protection
is active.
Modification access with no parameter change rights.
Access to a text array that does not exist (the parameter
value exists).
Access is temporarily not possible for unspecified reasons. –
Modification access with a value that is within the limits but
is illegal for other permanent reasons (parameter with
defined individual values).
The length of the present response exceeds the maximum
transfer length.
Illegal or unsupported value for attribute, number of
elements, parameter number, subindex or a combination
of these.
Write request: illegal or unsupported parameter data
format.
Write request: a mismatch exists between the number of
values in the parameter data and the number of elements
in the parameter address.
You have attempted to access a drive object that does not
exist.
Illegal or unknown request ID.
You have tried to access a parameter that, although
available, does not currently perform a function
(e.g., n control set and access to a V/f control parameter).
Operating Instructions, 12/2018, A5E36652151A
Additional
info
Subindex
Subindex
Subindex
Subindex
Subindex
Subindex
Enclosed Drives

Advertisement

Table of Contents
loading

Table of Contents