General Information About Profinet Io For Sinamics - Siemens SINAMICS S150 NEMA Operating Instructions Manual

Converter cabinet units
Hide thumbs Also See for SINAMICS S150 NEMA:
Table of Contents

Advertisement

Operation
6.9 Communication via PROFINET IO
6.9.2
General information about PROFINET IO
6.9.2.1

General information about PROFINET IO for SINAMICS

General information
PROFINET IO is an open Industrial Ethernet standard for a wide range of production and
process automation applications. PROFINET IO is based on Industrial Ethernet and
observes TCP/IP and IT standards.
Deterministic signal processing in real time is important in industrial networks. PROFINET IO
satisfies these requirements.
International standard IEC 61158 ensures open, multi-vendor systems
PROFINET IO is optimized for high-speed, time-critical data communication at field level.
PROFINET IO
Within the context of Totally Integrated Automation (TIA), PROFINET IO is the systematic
development of the following:
● PROFIBUS DP, the established fieldbus,
● Industrial Ethernet, the communications bus for the cell level.
Experience gained from both systems was integrated into PROFINET IO. As an Ethernet-
based automation standard defined by PROFIBUS International (PROFIBUS user organiza-
tion), PROFINET IO is a manufacturer-independent communication and engineering model.
PROFINET IO defines every aspect of the data exchange between IO controllers (devices
with so-called "master functionality") and the IO devices (devices with so-called "slave
functionality") as well as carrying out parameterization and diagnostics. A PROFINET IO
system is configured in virtually the same way as a PROFIBUS system.
A PROFINET IO system is made up of the following devices:
● The IO controller controls automation tasks.
● An IO Device is controlled and monitored by an IO controller. An IO device can consist of
several modules and submodules.
● An IO Supervisor is an engineering tool, typically based on a PC, with which the individual
IO devices (drive unit) are parameterized and diagnosed.
IO devices: Drive units with PROFINET interface
● SINAMICS S150 with CU320-2 DP and inserted CBE20
● SINAMICS S150 with CU320-2 PN
With SINAMICS S150 and CBE20 or with CU320-2 PN, communication via PROFINET IO
with RT is possible.