General information about PROFINET IO

General information
PROFINET IO is an open Industrial Ethernet standard for a wide range of production and
process automation applications. PROFINET IO is based on Industrial Ethernet and
observes TCP/IP and IT standards.
Deterministic signal processing in real time is important in industrial networks. PROFINET IO
satisfies these requirements.
International standard IEC 61158 ensures open, multi-vendor systems.
PROFINET IO is optimized for high-speed, time-critical data communication at field level.
PROFINET IO
Within the context of Totally Integrated Automation (TIA), PROFINET IO is the systematic
development of the following systems:
● PROFIBUS DP, the established fieldbus
● Industrial Ethernet, the communications bus for the cell level.
Experience gained from both systems was integrated into PROFINET IO. An Ethernet-based
automation standard defined by PROFIBUS International (PROFIBUS user organization),
PROFINET IO is a manufacturer-independent communication and engineering model.
PROFINET IO defines every aspect of the data exchange between IO controllers (devices
with what is known as "master functionality" and the IO devices (those with what is known as
"slave functionality") as well as carrying out parameterization and diagnostics. A PROFINET
IO system is configured in virtually the same way as a PROFIBUS system.
A PROFINET IO system is assembled from the following devices:
● An IO controller controls automation tasks.
● An IO device is controlled and monitored by an IO controller. An IO device consists of
several modules and submodules.
● An IO supervisor is an engineering tool, typically based on a PC, with which the individual
IO devices (drive units) are parameterized and diagnosed.
IO devices: Drive units with PROFINET interface
● SINAMICS DCM with inserted CBE20
Cyclic communication using PROFINET IO with IRT or using RT is possible on all drive units
equipped with a PROFINET interface. This means that error-free communication using other
standard protocols is guaranteed within the same network.
SINAMICS DCM DC Converter
Operating Instructions, 12/2018, A5E34763375A
Descriptions of functions
10.5 Communication via PROFINET IO
491