H4: Analog Outputs; H5: Memobus/Modbus Serial Communication - YASKAWA A1000 HHP Programming Manual

High performance vector control drive
Table of Contents

Advertisement

u

H4: Analog Outputs

No.
(Addr.
Name
Hex)
Multi-Function Analog
H4-01
Output Terminal FM
(41D)
Monitor Selection
H4-02
Multi-Function Analog
(41E)
Output Terminal FM Gain
H4-03
Multi-Function Analog
(41F)
Output Terminal FM Bias
Multi-Function Analog
H4-04
Output Terminal AM
(420)
Monitor Selection
H4-05
Multi-Function Analog
(421)
Output Terminal AM Gain
H4-06
Multi-Function Analog
(422)
Output Terminal AM Bias
Multi-Function Analog
H4-07
Output Terminal FM Signal
(423)
Level Selection
Multi-Function Analog
H4-08
Output Terminal AM Signal
(424)
Level Selection
u

H5: MEMOBUS/Modbus Serial Communication

No.
(Addr.
Name
Hex)
H5-01
(425)
Drive Node Address
<1>
H5-02
Communication Speed
(426)
Selection
H5-03
Communication Parity
(427)
Selection
YASKAWA ELECTRIC SIEP YEAHHP 01B YASKAWA AC Drive – A1000 HHP Programming Manual
Description
All Modes
Selects the data to be output through multi-function analog output terminal
FM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter "103" for U1-03.
All Modes
Sets the signal level at terminal FM that is equal to 100% of the selected
monitor value.
All Modes
Sets the signal level at terminal FM that is equal to 0% of the selected monitor
value.
All Modes
Selects the data to be output through multi-function analog output terminal
AM.
Set the desired monitor parameter to the digits available in Uo-oo.
For example, enter "103" for U1-03.
All Modes
Sets the signal level at terminal AM that is equal to 100% of the selected
monitor value.
All Modes
Sets the signal level at terminal AM that is equal to 0% of the selected monitor
value.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
0: 0 to 10 V
1: -10 to 10 V
Description
All Modes
Selects drive station node number (address) for MEMOBUS/Modbus
terminals R+, R-, S+, S-. Cycle power for the setting to take effect.
All Modes
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
All Modes
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
A.9 H Parameters: Multi-Function Terminals
Values
Page
Default: 102
121
Range: 000 to 999
Default: 100.0%
Min.: -999.9
121
Max.: 999.9
Default: 0.0%
Min.: -999.9
121
Max.: 999.9
Default: 103
121
Range: 000 to 999
Default: 50.0%
Min.: -999.9
121
Max.: 999.9
Default: 0.0%
Min.: -999.9
121
Max.: 999.9
Default: 0
122
Range: 0, 1
Default: 0
122
Range: 0, 1
Values
Page
Default: 1F (Hex)
Min.: 0
122
Max.: FF
Default: 3
123
Range: 0 to 8
Default: 0
123
Range: 0 to 2
279