Removing The Bbu Holder From The Chassis - Fujitsu PRIMERGY TX300 S7 Upgrade And Maintenance Manual

Table of Contents

Advertisement

Ê Remove the air duct as described in section
on page
92.
Ê Remove the system fan holder as described in section
system fan holder" on page
9.6.4.3

Removing the BBU holder from the chassis

Figure 328: Removing the BBU holder from the chassis
Ê Carefully disconnect the BBU cable from the RAID controller.
Ê Remove the BBU cable from the cable guide.
Ê Lift up the green locking handle on the BBU holder (1, see close-up) while
sliding the BBU holder towards the server front as far as it will go (2).
I
After that, the fixation bolts on the chassis floor will rest in the wide
ends of the keyhole slots on the holder.
Ê Lift the BBU holder out of the chassis.
TX300 S7 / RX350 S7
378.
Upgrade and Maintenance Manual
Expansion cards and backup units
"Removing the system air duct"
"Removing the
507