62
Introduction to PoE
PSU Supervision
AC Input Alarm
Thresholds
Configuration
AC Input Alarm
Thresholds
Configuration Tasks
AC Input Alarm
Thresholds
Configuration Example
P
E PSU S
O
C
ONFIGURATION
The PoE-capable Switch 8800 Family series can monitor the external PoE PSUs
through the power supervision module on the PoE external power system.
The PoE PSU supervision module enables you to:
Set the alarm thresholds for the AC input voltages of the PoE PSUs.
Set the alarm thresholds for the DC output voltages of the PoE PSUs.
Query PSU information such as voltage and power.
You can set the AC input alarm thresholds for the PoE PSUs to enable the Switch
8800 Family series to monitor the AC input voltages of the PSUs in real time
through the PoE supervision module.
Table 671 AC input alarm thresholds configuration tasks
No Operation
1
Enter system view
Set the overvoltage alarm
threshold of AC input
2
(upper threshold) for the
PoE PSUs
Set the undervoltage alarm
3
threshold of AC input (lower
threshold) for the PoE PSUs
Display the AC input state of
4
each PoE PSU
n
You can set the thresholds to any appropriate values in the range, but make
sure the lower threshold is less than the upper threshold.
For 220 VAC input, it is recommended to set the upper threshold to 264 V and
the lower threshold to 181 V.
For 110 VAC input, it is recommended to set the upper threshold to 132 V and
the lower threshold to 90 V.
Network requirements
Set the overvoltage alarm threshold of AC input for PoE PSUs to 264.0 V.
Set the undervoltage alarm threshold of AC input for PoE PSUs to 181.0 V.
UPERVISION
Command
system-view
poe-power input-thresh
upper string
poe-power input-thresh
lower string
display poe-power
ac-input state
Description
-
Required, and the max
voltage is 264.0 V.
Required, and the min
voltage is 90.0 V.
Optional, and you can
execute this command in
any view.