Commissioning (Startdrive)
11.7 Differences between offline and online parameterization
11.7

Differences between offline and online parameterization

Overview
All offline settings and therefore all data relating to parameterization, device configuration and
quick startup must be loaded to the converter in order to take effect.
To parameterize commissioning parameters in online mode, the editing mode must be
activated. Restore points are created during parameterization. If the online connection to
the converter is lost and a new connection is established, editing can continue from the most
recently backed-up parameterization status.
Safety Integrated Functions
In the offline and online modes, Safety Integrated Functions can only be configured if the edit
mode is activated.
After completion of offline editing, the configuration can be loaded into the converter and
executed without any further postprocessing.
Requirement
• The drive has been completely created and specified in the device configuration.
• For the online parameterization:
There is an active online connection between the converter and the operating unit.
• Activate editing:
Only possible if access is exclusively via the currently connected operating unit.
Editing cannot be activated if the converter is being simultaneously accessed by multiple
operating units via Startdrive or the web server. The converter indicates that other accesses
are active and refuses to activate editing.
• Access if project protection is activated:
If project protection is activated, authentication is required.
The rights required for editing are assigned to your user account and activated.
Activate/finish editing
Display
Description
Editing mode is not activated.
Start editing with
Editing mode is activated.
Finish editing with
Note
When editing finishes, a new restore point is created automatically. The current configuration is stored in a
power-independent manner.