Connecting
7.1 Line system, motor and braking resistor
Converter
6SL4113-..□□-..F0
-..□□-
Frame
Rated power
size
in kW
23 ... 24
D2
30 ... 37
26 ... 27
E
45 ... 55
Table 7-8
Line supply cable connection (line voltage 3AC 380 ... 415 / 3AC 440 ... 500 V, IP 20)
Converter
6SL4113-..□□-..F0
-..□□-
Frame
size
08 ... 13
A
15 ... 16
B
17 ...18
C
20 ... 21
D1
23 ... 24
D2
26 ... 27
E
Table 7-9
Protective conductor connection in terminal X1 (line voltage 3AC 380 ... 415 / 3AC 440 ... 500 V, IP 20)
Converter
6SL4113-..□□-..F0
-..□□-
Frame
size
08 ... 13
A
15 ... 16
B
17 ...18
C
20 ... 21
D1
23 ... 24
D2
26 ... 27
E
Table 7-10
Protective conductor connection in terminal X2 (line voltage 3AC 380 ... 415 / 3AC 440 ... 500 V, IP 20)
Converter
6SL4113-..□□-..F0
-..□□-
Frame
size
08 ... 13
A
15 ... 16
B
17 ...18
C
156
Connection at the converter for the motor
Conductor cross-
section in mm²
(AWG)
10 ... 50 (7 ... 1/0)
35 ... 95 (2 ... 3/0)
Line supply cable
Rated power
Conductor cross-
in kW
section in mm²
(AWG)
1.1... 4
1.5 ... 4 (15 ... 11)
5.5 ... 7.5 
4 ... 6 (11 ... 9)
11 ... 15
6 ... 16 (9 ... 5)
18.5 ... 22
6 ... 35 (9 ... 2)
30 ... 37
10 ... 50 (7 ... 1/0)
45 ... 55
35 ... 95 (2 ... 3/0)
Protective conductor connection in terminal X1
Rated power in
Conductor cross-sec‐
kW
tion in mm² (AWG)
1.1... 4
1.5 ... 4 (15 ... 11)
5.5 ... 7.5 
1.5 ... 6 (15 ... 9)
11 ... 15
1.5 ... 16 (15 ... 5)
18.5 ... 22
1.5 ... 35 (15 ... 2)
30 ... 37
1.5 ... 50 (15 ... 1/0)
45 ... 55
2.5 ... 95 (13 ... 3/0)
Protective conductor connection in terminal X2
Rated power in
Conductor cross-sec‐
kW
tion in mm² (AWG)
1.1... 4
1.5 ... 4 (15 ... 11)
5.5 ... 7.5 
1.5 ... 6 (15 ... 9)
11 ... 15
1.5 ... 16 (15 ... 5)
Tightening torque in
Stripped
Nm (lbf in)
length in mm
(in)
5 ... 6 (44.3 ... 53.1)
19 (0.7)
10 ... 12 (88.5 ... 106.2) 25 (1)
Tightening torque in
Nm (lbf in)
0.4 ... 0.5 (3.5 ... 4.4)
0.5 ... 0.6 (4.4 ... 5.3)
1.2 ... 2 (5.3 ... 17.7)
3.8 ... 4 (33.6 ... 39.8)
5 ... 6 (44.3 ... 53.1)
10 ... 12 (88.5 ... 106.2) 25 (1)
Tightening torque in
Nm (lbf in)
2 ... 3 (17.7 ... 26.6)
2 ... 3 (17.7 ... 26.6)
2 ... 3 (17.7 ... 26.6)
4 ... 5 (35.4 ... 44.3)
4 ... 5 (35.4 ... 44.3)
4 ... 5 (35.4 ... 44.3)
Tightening torque in
Nm (lbf in)
2 ... 3 (17.7 ... 26.6)
2 ... 3 (17.7 ... 26.6)
2 ... 3 (17.7 ... 26.6)
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Connection type
Screw terminal
Screw terminal
Stripped
Connection type
length in mm
(in)
7 (0.3)
Screw terminal
12 (0.5)
Screw terminal
10 (0.4)
Screw terminal
18 (0.7)
Screw terminal
19 (0.7)
Screw terminal
Screw terminal
Connection type
M4, screw terminal, outside
M4, screw terminal, outside
M4, screw terminal, outside
M5, screw terminal, outside
M5, screw terminal, outside
M5, screw terminal, outside
Connection type
M4, screw terminal, outside
M4, screw terminal, outside
M4, screw terminal, outside