Siemens SINAMICS G220 Operating Instructions Manual page 727

Table of Contents

Advertisement

5. The converter closes the K1 converter contactor.
6. The converter performs a flying restart of the motor. The output frequency of the converter
synchronizes with the motor speed.
If the "Flying restart" function is deactivated, the motor coasts down and the converter
outputs alarm A07314.
Example
The figure below shows an example of the wiring of the converter and the internal
interconnections of the inputs and outputs.
K1
K2
Figure 14-263
Parameters
The following list contains the parameters of the "Bypass" function.
Number
p1260
r1261.0...14
p1262[0...n]
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
K1: Contactor between the converter and the motor
K2: Bypass contactor between the line supply and the motor
Wiring for the "Bypass" function
Name
Bypass configuration
Bypass control/status word
Bypass dead time
Functions
14.13 Technology functions
Unit
 
 
[s]
725