Converter
6SL4113-..□□-..F0
-..□□-
Frame
size
20 ... 21
D1
23 ... 24
D2
26 ... 27
E
7.1.4

Connecting an IP55 converter

7.1.4.1

Remove and install housing cover, converter with IP55 degree of protection

Overview
To connect cables or replace converter components, you must remove the converter housing
cover.
Removing and installing the housing cover is identical for all converter frame sizes.
The following procedure describes removing and installing the housing cover using a
converter, frame size FSC as example.
Requirement
The following requirements apply when the housing cover is removed:
• Comply with ESD regulations.
• Required tools:
– Torx screwdriver T20
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Protective conductor connection in terminal X2
Rated power in
Conductor cross-sec‐
kW
tion in mm² (AWG)
18.5 ... 22
1.5 ... 35 (15 ... 2)
30 ... 37
1.5 ... 50 (15 ... 1/0)
45 ... 55
2.5 ... 95 (13 ... 3/0)
7.1 Line system, motor and braking resistor
Tightening torque in
Connection type
Nm (lbf in)
4 ... 5 (35.4 ... 44.3)
M5, screw terminal, outside
4 ... 5 (35.4 ... 44.3)
M5, screw terminal, outside
4 ... 5 (35.4 ... 44.3)
M5, screw terminal, outside
Connecting
157