Response Times When Controlling Via Profisafe - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

The specified response times are applicable for a fault-free drive system as well as when a
fault is active in the system.
Table 17-21
Function
SDI and SLS
SSM (output to the bus)
SSM (output at terminals)
SMT
p9500: Monitoring cycle (factory setting: 4 ms)
t_R:
p9545: SSM filter time
t_K
2
17.11.4

Response times when controlling via PROFIsafe

Technical data
The response times are converter-internal response times. Program runtimes in the F‑host and
the transmission time via PROFINET are not taken into account. Consider the following with
regard to the calculation of the response times between F-CPU and converter: Safety Integrated
Functions are only selected after the PROFIsafe monitoring time (F_WD_Time) has elapsed, e.g.
due to communication faults. The PROFIsafe monitoring time (F_WD_Time) must therefore also
be included as a relevant component in the calculation when an error occurs.
Notes regarding understanding the following table
The specified response times are applicable for a fault-free drive system as well as when a
fault is active in the system.
• Worst Case Delay Time (WCDT): Maximum response time between a PROFIsafe telegram
being received and a stop function being initiated when there is no fault
• One Fault Delay Time (OFDT): Maximum response time between a PROFIsafe telegram being
received and a stop function being initiated when a fault is active
• Watchdog Time (WDTime): Time between receiving the last valid PROFIsafe telegram and the
initiation of a stop function after the PROFIsafe monitoring time elapses
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Technical data - Response times
Motor overtemperature or internal
error
Short-circuit or wire break
t_R depends on the relevant stop response initiated after the limit is breached:
• STO: 0.5 ms
• SS1: 2 ms
:
Time for the internal converter communication when sending a PROFIsafe telegram
• For isochronous communication: t_K
ration on the control side.
• For non-isochronous communication: t_K
17.11 Safety Integrated Functions
Unit
Worst case delay time
ms
(3 · p9500) + t_R
ms
(3 · p9500) + p9545 + t_K
ms
(2 · p9500) + p9545 + 1.5
ms
300
s
1
 =T
. Determine T
2
dp
 = 4 ms
2
Technical data
2
 from the bus configu‐
dp
821

Advertisement

Table of Contents
loading

Table of Contents