Description of function
If the converter detects a logical error in an access attempt, it responds with the following two
bytes in the protocol data unit:
• Byte 1: Highest bit in function code = 1
• Byte 2: Error code
Table 14-44
Error code
01
02
03
04
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Overview of the error codes
Name
Invalid function code
Invalid register
Invalid data value
General error
14.5 Modbus TCP communication
Possible error causes
The controller has sent a function code that is not sup‐
ported by the converter.
The current UMAC settings do not contain any write or
read permissions.
The controller is attempting to access an invalid register.
The range defined by the starting register and the num‐
ber of registers contains one or more invalid registers.
The controller is addressing more than 125 registers.
Write access to a "Read only" register
Write access to a reserved register