Functions
14.12 Safety Integrated
Figure 14-231
670
SLS with change between two SLS limit values
Action
Selection of SLS
Braking below the SLS limit
value
Activation of the SLS limit val‐
ue
Violation of the SLS limit
Change to SLS1 limit value
Braking below the SLS limit
value
Motor/converter response
The converter detects the selection of SLS.
The converter detects when the SLS2 limit value is selected.
The converter starts the SLS delay time (p9551).
The motor follows the setpoint of the higher-level control and
brakes.
2)
The actual speed must remain below the SLS2 limit value until
the SLS delay time has elapsed.
Monitoring of the SLS2 limit value (p9531[1)] is effective once
the SLS delay time (p9551) has elapsed.
The converter signals the status "SLS active" (r9722.4) and the
active SLS level (r9722.9 = 1, r9722.10 = 0).
If the motor speed violates the SLS2 limit value, the converter
initiates the set stop response p9563[1].
The converter detects when the SLS1 limit value is selected.
The converter starts the SLS delay time (p9551). The SLS2 limit
value remains while the SLS delay time is active.
The motor follows the setpoint of the higher-level control and
brakes.
2)
The actual speed must remain below the SLS1 limit value until
the SLS delay time has elapsed.
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
1)
1) 3)
SINAMICS G220 converter