Application planning
4.14 EMC-compliant installation
4.14.10
Maximum permissible signal cable lengths, converter in degree of
protection IP55
Technical data
Table 4-6
Connection at the converter
24 V supply (terminals X124:1...
4)
Digital input
Failsafe digital input
Digital output DO 0
Relay output DO 1, DO 2
Failsafe digital output
Temperature sensor
Analog input
Analog output
10 V output voltage
24 V output voltage
Fieldbus
DRIVE-CLiQ
4.14.11

Maximum permissible signal cable lengths, option module OM-SMT

Requirement
Only cables with an insulation that is designed for an ambient temperature of 75 °C are
permissible.
Technical data
Sensor cable
Without short-circuit detection
With short-circuit detection
≤ 1 000 m for the temperature monitoring of explosion-protected motors, i.e. to comply with guideline
1)
2014/34/EU (ATEX) or regulation 2016 No. 1107 (UKEX)
90
Maximum permissible signal cable lengths, IP55
Cable length
If conducted disturbances occur on the 24V cable, we recommend
using a Schurter FPBB 3-103-715 line filter
The maximum permissible connecting cable length is 1000 m.
The maximum permissible connection cable length is 300 m.
The maximum permissible connection cable length is 30 m.
The maximum permissible connecting cable length is 1000 m.
The maximum permissible connection cable length is 100 m.
The maximum permissible connection cable length is 100 m.
Cable length (copper cable)
≤ 500 m
≤ 1 500 m
≤ 2 500 m
≤ 50 m
≤ 150 m
≤ 250 m
1)
1)
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Cable cross-section
0.5 mm² / AWG 21
1.5 mm² / AWG 16
2.5 mm² / AWG 14
0.5 mm² / AWG 21
1.5 mm² / AWG 16
2.5 mm² / AWG 14