12.3

Series commissioning using the web server

Overview
For "Series commissioning using the web server" transfer the settings of converter 1 using the
web server to converter 2 or to additional converters.
Procedure
Proceed as follows to perform series commissioning using the web server:
1. Switch on the supply voltage of converter 1.
2. Commission the converter using your operating unit, e.g. a PC.
You can find more information in Chapter "Commissioning (web server) (Page 209)".
3. Save the settings retentively once commissioning has been completed via
4. Call the "Backup and restore" menu.
5. Click the "Create backup" button in the "Save drive data to backup file" area.
Optional: Assign a name for the backup file.
The drive data are backed up in the backup file in the download folder of your operating unit.
6. Switch on the supply voltage of converter 2.
7. In the web browser, enter the IP address of the converter 2, e.g. https://169.254.11.22.
You determine the IP address of the converter 2, e.g. using the integrated
SINAMICS SDI Standard. You can find more information in Chapter "Scanning the IP address
(Page 317)".
The web server of converter 2 displays page "Basic settings".
8. Make the basic settings for converter 2.
You can find more information in Chapter "Basic settings (Page 214)".
9. In the Security Wizard, select option "Exit the Security Wizard and continue with low security
settings".
10.Call the "Backup and restore" menu.
11.Click the "Click to select file, or drag and drop file here" button to select the backup file.
12.Click on "Restore".
Converter 2 takes the settings from the backup file.
After a restart, the security settings configured in converter 1, e.g. drive password, UMAC
data, become active in converter 2.
Repeat steps 6 to 12 for all additional converters to which you wish to transfer the settings of
converter 1.
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
12.3 Series commissioning using the web server
Series commissioning
.
299