Siemens SINAMICS G220 Operating Instructions Manual page 347

Table of Contents

Advertisement

Bit
08
09
10
11
12
13
14
15
Parameters
The following list contains the parameters of the "Control and status word 1" function.
Number
r0056.0...15
c0810
r0836.0...3
c0840[0...n]
c0844[0...n]
c0848[0...n]
c0852[0...n]
c0854[0...n]
r0899.0...13
c1035[0...n]
c1036[0...n]
c1113[0...n]
c1140[0...n]
c1141[0...n]
c1142[0...n]
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Status
1 = Speed deviation within the tolerance range
1 = Control request
1 = Comparison speed reached or exceeded
Telegrams
Telegram 20
102, 103
1 = Alarm class
1 = Current or
bit 0
torque limit
reached
1 = Alarm class
---
bit 1
Telegrams
All other telegrams
102, 103
Reserved
0 = Alarm motor overtemperature
1 = Torque con‐
1 = Motor rotates clockwise
trol active
0 = Motor rotates counter-clockwise Converter-internal actual value < 0
Telegrams
Telegram 20
102, 103
Reserved
1 = CDS display
Name
Status word, closed-loop control
Command data set selection CDS bit 0
Command Data Set CDS selected
ON / OFF (OFF1)
No coast-down / coast-down (OFF2) signal 1
No Quick Stop / Quick Stop (OFF3) signal 1
Enable operation/inhibit operation
Control by PLC/no control by PLC
Status word sequence control
Motorized potentiometer setpoint raise
Motorized potentiometer lower setpoint
Setpoint inversion
Enable ramp-function generator/inhibit ramp-function
generator
Continue ramp-function generator/freeze ramp-function
generator
Enable setpoint/inhibit setpoint
Status word 1 (ZSW1)
Converter → Control
Explanation
Setpoint/actual value deviation within
the tolerance range.
The automation system has been reques‐
ted to take over control of the converter.
Speed is greater than or equal to the cor‐
responding maximum speed.
All other tele‐
Comparison value for current or torque
grams
has been reached or exceeded.
1 = Torque limit
reached
1 = Holding
Signal for opening and closing a motor
brake open
holding brake.
--
Converter-internal actual value > 0.
All other tele‐
 
grams
0 = Alarm con‐
verter thermal
overload
Functions
14.4 PROFINET communication
Unit
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
345