Restore Factory Settings - Siemens SINAMICS G220 Operating Instructions Manual

Table of Contents

Advertisement

– Enter the drive password that was used to encrypt the drive data in the backup file.
– The converter takes the drive data from the backup file.
10.5.5.6

Restore factory settings

Overview
The "Restore factory settings" function deletes the user-specific parameterization of the
converter, for example the motor data.
The following data remains in the converter:
• Communication interface settings
• Security settings including UMAC data
• Language setting
• Date and time
In the following cases it may be necessary to restore the converter to factory settings:
• Difference in topology when replacing a motor with/without DRIVE-CLiQ interface
• Uncertainty regarding the previous parameterization or the previous use of the converter
Requirement
Requirements:
• Before carrying out a reset, save the drive data in a backup file so that you can access the
settings again.
• Rights required for active user management (UMAC):
– "Edit device configuration or drive applications"
– If Safety Integrated is contained in the backup file, the "Edit Safety Integrated application"
Procedure
Proceed as follows to reset the drive settings to the factory settings:
1. Call the "Backup and restore" menu.
2. Press the "Restore factory settings" button.
3. Acknowledge the confirmation prompt.
4. The converter resets its drive settings to the factory settings.
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
The settings at the time of the backup are restored.
Function "Drive data encryption" is activated.
The originally configured drive password is applied.
right is required.
Commissioning (web server)
10.5 Functions and menus
261