Siemens SINAMICS G220 Operating Instructions Manual page 613

Table of Contents

Advertisement

t
W
Figure 14-196
Parameters
The following list contains the parameters of the "Automatic restart" function.
Number
r0056.0...15
p1206[0...9]
p1210
p1211
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Sum of the magnetizing time and the time for the flying restart of the motor
A fault activates the automatic restart function.
1st attempt of the automatic restart starts.
The converter decrements the counter of the automatic restart attempts.
Fault F07320 is output if the counter value of the restart attempts < 0
1st attempt of the automatic restart fails as a result of a new fault.
2nd attempt of the automatic restart starts.
2nd attempt of the automatic restart is successful.
If no fault has occurred one second after the flying restart of the motor, then the automatic restart
attempt was successful.
The automatic restart must be successful within p1213[0]. If not, fault F07320 is output
After p1213[1], the converter resets the automatic restart attempts to p1211.
Time response of the automatic restart
Name
Status word, closed-loop control
Automatic restart faults not active
Automatic restart mode
Automatic restart start attempts
Functions
14.11 Drive functions
Unit
 
 
 
 
611