Functions
14.12 Safety Integrated
Parameters
The following list contains the parameters of the "Safe Motor Temperature (SMT)" function.
Number
p9604.0...30
14.12.7

Selection of the Safety Integrated Functions

Overview
The function selection offers the following setting options:
• Enable and inhibit each Safety Integrated Function
• Actual value acquisition and monitoring cycle
• Defining the axis type
Requirement
Certain Safety Integrated Functions require a license.
The SMT function requires the OM-SMT Option Module.
Description of function
Table 14-93
Safety Integrated Functions for every control type
Control type
PROFIsafe
PROFIsafe and Emergency
Stop via terminals
Terminals
The Safety Integrated Function requires the "Safety Extended" license.
STO is enabled in the factory setting, and preassigned at failsafe digital input F-DI 0. When delivered, wire jumpers are inserted
1)
at the F-DI 0. When using STO, remove the wire jumpers from F-DI 0 and connect an appropriate sensor (e.g. Emergency Stop
pushbutton). The wire jumpers remain inserted at the F-DI 0 if STO is not used.
2)
SS1-t does not require a license. SS1-a and SS1-r require a license.
Safety Integrated Functions are enabled with factory settings after function selection
(p9604).
The stop responses (STO and SS1) must always be parameterized because the stop responses
stop the motor in the event of an error and for a limit value violation. If the STO and SS1
functions are also to be controlled via PROFIsafe and/or F-DI, then STO and SS1 must also be
enabled.
680
Name
SI enable
STO
SS1
1)
2)
x
x
x
x
x
x
SLS
SSM
x
x
x
x
x
x
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Unit
 
SDI
SMT
x
SMT is inde‐
pendent of
x
the control
type.
x
SINAMICS G220 converter