Siemens SINAMICS G220 Operating Instructions Manual page 773

Table of Contents

Advertisement

3. Switch on the converter power supply.
4. Wait until LED COM on the OM-IIoT lights up green.
5. Configure the IP address and the subnet mask of your PC.
PC and OM-IIoT must be in the same network segment.
6. In the file explorer of the PC, go to the folder in which you saved the upgrade package, e.g.
D:\IIOT\IIoT_upgrade\
7. Enter "cmd" + <↵> in the address bar of the file explorer.
8. The PC opens the command prompt in a new window:
D:\IIOT\IIoT_upgrade> _
9. Enter command "ping xxx.xxx.xxx.xxx" with the IP address of the OM-IIoT:
D:\IIOT\IIoT_upgrade> ping 169.254.1.42
10.If the PC and OM-IIoT are connected with one another, then the PC displays:
Pinging 169.254.1.42 with 32 bytes of data:
Reply from 169.254.1.42: bytes=32 time=22ms TTL=64
Reply from 169.254.1.42: bytes=32 time=22ms TTL=64
Reply from 169.254.1.42: bytes=32 time=22ms TTL=64
Reply from 169.254.1.42: bytes=32 time=22ms TTL=64
Ping statistics for 169.254.1.42:
Approximate round trip times in milli-seconds:
11.Enter command "sftp xx0@xxx.xxx.xxx.xxx":
D:\IIOT\IIoT_upgrade> sftp xx0@169.254.1.42
xx0@169.254.1.42's password:
SINAMICS G220 converter
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Minimum = 11 ms, Maximum = 22ms, Average = 13ms
16.4 Firmware update of option module OM-IIoT
Corrective maintenance
771