Functions
14.4 PROFINET communication
Description of function
Values in italics in the following tables mean that these values must be adapted to the specific
request.
Table 14-8
Request to change parameters
Data block
Header
Address, parameter 1
Address, parameter 2
...
Address, parameter m ...
Values, parameter 1
Values, parameter 2
...
Values, parameter m
Table 14-9
Response, if the converter has executed the change request
Data block
Header
372
Byte n
Reference 01 hex ... FF hex
01 hex (ID of drive objects, for G120 al‐
ways = 01 hex)
10 hex: Value of the parameter
Parameter number 0001 hex ... FFFF hex
Number of the 1st index 0000 hex ... FFFE hex
...
...
...
Format
02 hex: Integer 8
03 hex: Integer 16
04 hex: Integer 32
05 hex: Unsigned 8
06 hex: Unsigned 16
07 hex: Unsigned 32
08 hex: Floating Point
0A hex: Octet String
0D hex: Time Difference
34 hex: TimeOfDay without date indication
35 hex: TimeDifference with date indication
36 hex: TimeDifference without date indication
41 hex: Byte
42 hex: Word
43 hex: Double word
Value of the 1st index
...
...
...
...
Byte n
Reference (identical to a change request)
01 hex (ID of drive objects, for G120 al‐
ways = 01 hex)
Bytes n + 1
02 hex: Change request
Number of parameters (m) 01 hex ... 27 hex 2
Number of indices
00 hex ... EA hex
(00 hex and 01 hex are equivalents)
Number of index values
00 hex ... EA hex
Bytes n + 1
02 hex (change request successful)
Number of parameters (identical to a change
request)
Operating Instructions, 04/2024, FW V6.2, A5E51781573B AB
n
0
4
6
8
...
...
n
0
2
SINAMICS G220 converter