4.7. Identification & Maintenance (I&M)
4.7.1. General Information
Identification & Maintenance (I&M) provides a standard way of gathering information about an I/O device. The
I&M information can be accessed by the IO Controller by means of acyclic Record Data Read/Write services.
The application should provide application specific I&M0 information during start-up. See
(F6h) (page 112)
for more information.
It is possible for the application to handle I&M records. Activate this using the IM_Options command. See
Network PROFINET IO Object (0Eh) (page 59)
While I&M0 information describes the application, the I&M5 information describes the communication unit i.e.
the Anybus CompactCom 40 PROFINET IRT, to the PROFINET network. Most of the information is provided by
the module, but the application can change the order ID and the IM annotation (attributes #25 and #26, see
PROFINET IO Object (F6h) (page
enabled), see
PROFINET IO Object (F6h) (page
there as well, see below.
NOTE
I&M5 is not available for Anybus IP. See below how to disable I&M5 in the GSD file for Anybus IP.
Default I&M0 information:
IM Manufacturer ID
IM Order ID
IM Serial Number
IM Software Revision
IM Software Revision
IM Revision Counter
IM Profile ID
IM Profile Specific Type
IM Version
IM Supported
Disabling I&M5 in the GSD File
NOTE
I&M5 is always disabled and can not be enabled on Anybus IP. It has to be disabled in the example
GSD file, if this is to be used.
I&M5 is enabled by default in the GSD file.
The settings for I&M are located at the Device Access Point, within <VirtualSubmoduleItem...>. To
disable I&M5 , change GSDML entry <IM5_Supported="true"> to <IM5_Supported="false">.
Page 20 of 177
for more information.
112)). I&M5 is enabled by default, but can be disabled using attribute #27 (IM5
112). If the example GSD file is used, I&M5 has to be disabled
010Ch (HMS Industrial Networks)
"CompactCom 40 PIR"
(unique serial number, set during manufacturing)
(Anybus hardware revision ID, set during manufacturing)
(Anybus software revision, set during manufacturing)
(Revision counter)
0000h (Generic Device)
0004h (No profile)
0101h
For submodules belonging to a "non–zero API", the returned value is zero. For submodules belonging
to API 0, the returned value is 000Eh (IM0-3 supported)
Identification & Maintenance (I&M)
PROFINET IO Object
SCM-1202-021 Version 2.6