12.8.8 Power Loss Restart
Power loss restart
This function allows the converter to start running automatically after power on
if the converter was running before power off.
Related parameters:
Code
Name
E0.45 Power loss restart mode
E0.46 Power loss restart delay
Setting range of E0.45:
E0.45=0: Inactive
●
Power loss restart feature is disabled.
E0.45=1: Active for panel control
●
When [E0.01]/[E0.03] = 0 (Operating panel), if the converter is running be-
fore power off, then converter will automatically start after waiting for the
time of [E0.46] after power-on.
E0.45=2: Active for digital input control
●
When [E0.01]/[E0.03] = 1 (Multi-function digital input), if the converter is run-
ning before power off, then converter will automatically start after waiting for
the time of [E0.46] after power-on.
Power loss restart function is active for panel and digital input
●
control only.
When E0.45 select "1" or "2", if the power supply of frequency
●
converter and the error "UE-1" recover within the time of [E9.01],
the frequency converter will restart.
WARNING
The power loss restart function can make the frequency converter run automati-
cally after the power supply is restored, which may cause damage to people and
equipment.
Setting range
0: Inactive
1: Active for panel control
2: Active for digital input
control
0.0...10.0
The power loss restart function may cause dam-
age to people and equipment!
R912005854_Edition 09 Bosch Rexroth AG
Functions and Parameters
Default
Unit
Step
0
-
-
10.0
s
0.1
215/653
Attri.
Stop
Stop