Bosch rexroth EFC 610 Series Operating Instructions Manual page 593

Frequency converter
Hide thumbs Also See for rexroth EFC 610 Series:
Table of Contents

Advertisement

Rexroth Frequency Converter EFC x610
559/653
Series
Accessories
Fig. 15-53: Shielded cable connection with accessories for I, J housing (FEAM03.2-004-NN-
NNNN)
Connection steps
Step 1: Place holes ① of the connector on the two screw holes outside of sym-
bols
and tighten two screws.
Step 2: Insert the shielded cables through component ② of the connector with
the shielding layer reliable contact with the metal.
Step 3: Tighten four screws of the accessories.
Step 4 (Optional): Insert the STO cable through component ④ of the connector
with the shielding layer reliable contact with the metal.
Step 5 (Optional): Tighten two screws of the accessories.
R912005854_Edition 09 Bosch Rexroth AG