Functions and Parameters
If [H8.26] ≠ 11, EAO output mode is resumed to [H8.25] 'EAO output mode'
automatically.
Set the motor protection level
Set C1.73 'Motor thermal sensor protection level' according to the characteristic
of the temperature sensor. The setting value corresponds to the voltage value
detected by of analog input.
Example: If [C1.72] = 0, 2, 3, [C1.73] = 2, it represents 2 V, and the frequency
converter stops with error code 'Ot' displayed on the operating panel when the
voltage level on analog input is higher than 2 V; if [C1.72] = 4, [C1.73] = 2, it
represents 2 V, and the frequency converter stops with error code 'Ot' displayed
on the operating panel when the voltage level on analog input is lower than 2 V.
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Series