Rexroth Frequency Converter EFC x610
Series
Step 3: Reset the fan lifetime counter after fan maintenance or replacement
Set parameter C0.53 'Fan total running time reset' to '1: Active'.
●
After the execution, [C0.53] and [C0.51] will be reset to '0' automatically. By
now, the warning code 'FLE' is cleared completely.
Adjust the value of C0.52 'Fan maintenance time' if necessary.
●
If C0.50 = "0: Automatically controlled", when the converter runs, the
fan for electrolytic capacitor is switched on; When the converter
stops, the fan for electrolytic capacitor is switched off.
Functions and Parameters