Rexroth Frequency Converter EFC x610
Series
The output is inactive when the frequency converter without error / warning.
IO card relay output status is monitored by parameter d0.60 'Relay
output'.
12.22.6 I/O & I/O plus card diagnosis
This function is used to perform the self-test function of I/O & I/O plus card.
Code
Name
I/O card output channel
H8.87
diagnosis
Setting range of H8.87:
0: Inactive
●
The test is complete. All outputs are restored to default settings.
1: EAO diagnosis
●
The analog output of I/O & I/O plus card outputs 10 V.
2: EDO diagnosis
●
For I/O card, the open collector output of I/O card will have "Logic 1(High)"
output state.
For I/O plus card, the open collector output 1 of I/O plus card will have "Logic
1(High)" output state.
3: ERO diagnosis/EDO2 diagnosis
●
For I/O card, the relay output of I/O card is closed.
For I/O plus card, the open collector output 2 of I/O plus card will have "Logic
1(High)" output state.
4: All output diagnosis
●
EAO, ERO, EDO are all tested with the above methods.
Setting range
Default
0: Inactive
1: EAO diagnosis
2: EDO diagnosis
ERO diagnosis/EDO2
diagonis
All output diagnosis
R912005854_Edition 09 Bosch Rexroth AG
Functions and Parameters
Unit
Step
0
-
-
459/653
Attri.
Device
xFCx61
Stop
0