Rexroth Frequency Converter EFC x610
Series
Process Data Objects (PDO) Configuration
The following configuration shall be executed.
PDO1 mapping is static and hence it cannot be changed.
●
The default PDO mapping configuration is shown as below for Rexroth drive
●
profile.
RPDO
Mapping
No.
object index
1
0x6040
0x6040
2
0x6042
0x3770
3
0x377A
4
0x0000
TPDO
Mapping
No.
object index
1
0x6041
0x6041
2
0x6044
0x3771
3
0x23EA
4
0x0000
Tab. 12-83: PDO communication parameter structure for CiA-402 profile
Index
Sub
0
1
2
0x1400
3
4
5
0
0x1600
1
Tab. 12-84: RPDO1
**: When CiA-402 is enabled, the RPDO1 is enabled, so COB-ID gets
changed to 0x80000200 + Node-ID. RPDO1 is disabled in Rexroth
Profile. If enabled then it's erroneous.
Mapping object name
Control word
Control word
Target velocity (vl)
Drive control word
Frequency command
-
Mapping object name
Status word
Status word
vl control effort
Drive status word
Output frequency
-
Name
Number of entries
COB-ID used by PDO
Transmission type
Inhibit time (not implemented)
Reserved
Event timer
Number of mapped objects
Control word
Functions and Parameters
Comment
Controls the CiA-402 state machine
Controls the state machine and the
nominal speed (vl)
Controls the drive system state machine
and setting frequency
-
Comment
Shows the drive status
Shows status and the current speed (vl)
Shows the drive status and the current
output frequency
-
Default value
5
0x80000200 + Node-ID**
255
0
-
0
1
0x60400010
R912005854_Edition 09 Bosch Rexroth AG
359/653