Functions and Parameters

12.10.5 Frequency Detection Function

This function is used to detect the difference between the output frequency and
the setting frequency, the indication signal can be used for further engineering
in the application.
Code
Name
Frequency detection
E2.70
width
Frequency detection
E2.71
level FDT1
Frequency detection
E2.72
level FDT1 width
Frequency detection
E2.73
level FDT2
Frequency detection
E2.74
level FDT2 width
Frequency Arrival
Parameter E2.01, E2.15, H8.20, H8.21, H8.22, H9.00, H9.01, H9.02, H9.03 can
be set to '4: Speed arrival' to configure the digital outputs to show this func-
tion.
The 'Speed arrival' signal is active on the selected output terminal when the
difference between the 'Output frequency' and the 'Setting frequency' is with-
in the range set by parameter E2.70 'Frequency detection width':
Fig. 12-90: Frequency arrival
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Setting range
0.00...400.00 Hz
0.00...400.00 Hz
0.00...[E2.71] Hz
0.00...400.00 Hz
0.00...[E2.73] Hz
Default
Unit
Step
2.50
Hz
0.01
50.00
Hz
0.01
1.00
Hz
0.01
25.00
Hz
0.01
1.00
Hz
0.01
Series
Attri.
Run
Run
Run
Run
Run