Frequency Converter Mounting; Installation Conditions - Bosch rexroth EFC 610 Series Operating Instructions Manual

Frequency converter
Hide thumbs Also See for rexroth EFC 610 Series:
Table of Contents

Advertisement

36/653

Frequency Converter Mounting

7 Frequency Converter Mounting

7.1 Installation Conditions

The frequency converter must be vertically installed.
If one frequency converter is arranged above another, make sure the upper limit
of air temperature into the inlet is not exceeded (see
on page
24). An air guide is recommended between the frequency converters to
prevent the rising hot air being drawn into the upper frequency converter if the
upper limit of air temperature is exceeded.
Fig. 7-1: Mounting distance and arrangement
d
(Distance horizontal):
hor
d
= 0 mm (0K40...22K0); d
hor
d
(Minimum top distance):
top
d
= 125 mm (0K40...90K0); d
top
d
(Minimum bottom distance):
bot
d
= 125 mm (0K40...90K0); d
bot
1: Air inlet at frequency converter; 2: Air inlet at control cabinet
3: Frequency converter; 4: Air outlet at frequency converter
5: Heated air conveying direction; 6: Air guide in control cabinet
7: Fan in control cabinet; 8: Discharge of heated air
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
= 10 mm (30K0...160K)
hor
= 400 mm (110K...160K)
top
= 400 mm (110K...160K)
bot
chapter 6.1.9 "Conditions"
Series

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth efc 3610Rexroth efc 5610

Table of Contents