12.2.13 Power Loss Ride-Through

This function is helpful for continuing running of frequency converter when tem-
porary power loss occurs.
Code
Name
Power loss ride-through
C0.40
mode
Power loss ride-through
C0.41
recovery delay
Power loss ride-through
C0.42
action voltage
Power loss ride-through
C0.43
recover voltage
Power loss ride-through
C0.44
deceleration time
When AC power is lost or not stable for a short time, the frequency converter
will enter the power fault ride-through mode as long as the DC-bus voltage is
still maintained stable:
For 1P 200 VAC, DC-bus voltage is above 180 V
For 3P 380 VAC, DC-bus voltage above 370 V
The power fault ride-through operation will be decided by the selected options
as below:
1. The frequency converter output will be switched off
When the power supply resumes, the frequency converter will execute
speed capture and resume its previous operation, example for 3-Phase De-
vice actual minimum action voltage and recover voltage:
Setting range
0: Inactive
1: Output disabled
2: Regain kinetic energy
3: Regain kinetic energy, de-
celerate to stop
0.10...30.00 s
1P 200 VAC: 216...366 V
3P 200 VAC: 216...366 V
3P 380 VAC: 406...739 V
1P 200 VAC: 223...373 V
3P 200 VAC: 223...373 V
3P 380 VAC: 413...746 V
0.1...6000.0 s
R912005854_Edition 09 Bosch Rexroth AG
Functions and Parameters
Default
Unit
Step
0
-
-
0.50
s
0.01
240
V
1
440
250
V
1
450
5.0
s
0.1
147/653
Attri.
Stop
Stop
Stop
Stop
Stop