Bosch rexroth EFC 610 Series Operating Instructions Manual page 334

Frequency converter
Hide thumbs Also See for rexroth EFC 610 Series:
Table of Contents

Advertisement

300/653
Functions and Parameters
Communication control register (0x7F00)
The address of command word register for communication control is 0x7F00.
This register is write-only. The frequency converter is controlled through writing
data into the address. The definition of each bit is shown in table below:
bit
Value
15...9
1
8
0
1
7
0
1
6
0
1
5
0
1
4
0
1
3
0
1
2
0
1
1
0
1
0
0
Tab. 12-49: Communication control register (0x7F00)
If the communication frame check is successful (CRC valid), the frequency con-
verter always accepts the content of the control word. All conflicts (e.g. run
command and stop command active at the same time) are resolved by the appli-
cation functionality (Run / Stop generator, jog control...). This assures that the
frequency converter will always react in the same manner, independent of the
run command source.
Bosch Rexroth AG R912005854_Edition 09
Reserved
Torque control active
Inactive
Control word active
Inactive
Stop Acc. / Dec. active (stop the internal Acc. / Dec. ramp generator)
Inactive
Fault reset active
Inactive
E-stop active
Inactive
Stop according to parameter setting
Inactive
Reverse
Forward
Jog active (jogging direction determined by bit 2)
Inactive
Run command active
Inactive
Rexroth Frequency Converter EFC x610