Rexroth Frequency Converter EFC x610
Series
Fig. 12-116: CiA-402 state machine
Note:
Some of the CiA-402 states cannot be directly mapped to drive's internal sys-
tem state machine. More-over direct control of the drive's power section by
option card is not feasible. The states defined in the CiA-402 state machine
are simplified and mapped as follows.
CiA-402 state
Not ready to switch on
Switch on disabled / Ready to switch on / Switched on Stop
Operation enable
Quick stop active
Fault reaction active / Fault
Tab. 12-100: The state mapping of CiA-402 state machine
Quick stop object option code (0x605A) is not implemented.
Transition 16 is not supported.
Upon reception of Quick stop command the drive automatically transits (12)
to "Switch On Disabled" state when the drive stops.
Illegal state transition request is handled as follows:
In order to control the drive, the state transitions have to be done in a proper
sequence. If the requested state transition is not appropriate (as defined in
the state chart) then it is termed as "Illegal transition".
Functions and Parameters
Drive status
Initialization phase
Run
Run -> Stop transition
When error is set
R912005854_Edition 09 Bosch Rexroth AG
375/653