24/653
Frequency Converter Overview

6.1.9 Conditions

Rated ambient temperature
Derating / ambient temperature
Rated storage temperature
Rated altitude
Derating / altitude
Relative humidity
Degrees of protection
Degrees of pollution
Vibration
Mounting mode
Cooling type
Certification
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
-10...45 ℃
1.5 % / 1 °C (45...55 °C)
-20...60 ℃
≤ 1,000 m
1 % / 100 m (1,000...4,000 m)
≤ 90 % RH (No condensation)
IP 20 (Control cabinet mounting)
2 (EN 50178)
10 Hz ≤ f ≤ 57 Hz amplitude: 0.075 mm
57 Hz < f ≤ 150 Hz acceleration: 1 g
Wall mounting
DIN rail mounting
Natural cooling:
1P 200 / 3P 380 VAC: ≤ 0K75
3P 200 VAC: 0K40
Enforced air cooling:
1P 200 / 3P 380 VAC: ≥ 1K50
3P 200 VAC: 0K75...11K0
Cold plate:
1P200VAC 0.4...2.2kW
3P400VAC 0.4...4kW
CE (applicable to 0K40...160K)
UL/cUL (applicable to 0K40...160K)
EAC (applicable to 0K40...160K)
RCM (applicable to 0K40...90K0)