214/653
Functions and Parameters
If the threshold [E0.41] is set higher than the setting frequency
●
high limit [E0.09], the threshold will be limited to the high limit
[E0.09].
Make sure that:
●
1. The first and the second run command sources are both via
panel.
2. The active frequency setting source is via analog inputs.
3. The simple PLC, PID control and jog function are deactivated.
Otherwise, E0.35 'Starting mode' cannot be set to '3: Auto start /
stop according to setting frequency'. In this case, warning code
'PrSE' will be displayed and the frequency converter keeps in stop
status.
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Series