Bosch rexroth EFC 610 Series Operating Instructions Manual page 248

Frequency converter
Hide thumbs Also See for rexroth EFC 610 Series:
Table of Contents

Advertisement

214/653
Functions and Parameters
If the threshold [E0.41] is set higher than the setting frequency
high limit [E0.09], the threshold will be limited to the high limit
[E0.09].
Make sure that:
1. The first and the second run command sources are both via
panel.
2. The active frequency setting source is via analog inputs.
3. The simple PLC, PID control and jog function are deactivated.
Otherwise, E0.35 'Starting mode' cannot be set to '3: Auto start /
stop according to setting frequency'. In this case, warning code
'PrSE' will be displayed and the frequency converter keeps in stop
status.
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Series

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth efc 3610Rexroth efc 5610

Table of Contents