Functions and Parameters
Fig. 12-11: Hysteresis
The hysteresis for different models is as listed below:
1P 200 VAC / 3P 200 VAC: 10 V
●
3P 380 VAC: 15 V
●
For power size >= 30 kW, there is no internal brake chopper, [C0.15]
and [C0.16] are not visible.
12.2.7 Overvoltage suppression
This function is used to adjust the active slip compensation factor in order to
match the higher mechanical speed due to reciprocating load characteristic.
Code
Name
Overvoltage suppression ad-
C0.23
justment gain
Basic principle of reciprocating load application:
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Setting range
Default
0.00...10.00
1.00
Series
Unit
Step
Attri.
–
0.01
Run