Rexroth Frequency Converter EFC x610
Series

Acyclic Communication

Principle
Acyclic communication is mainly used for parameter read/write accesses from
controller, supervisor etc. The PROFINET service "read/write record" (RPC over
UDP) is utilized to realize the object addressing.
With the SFB52 "RDREC" and SFB53 "WRREC", a data record with the number
INDEX can be read from or written to a PROFINET IO device module defined by
ID. The key arguments ID and INDEX are described below.
When parameter write access on the two bytes type parameter, any
values exceed 65,535 (0xFFFF) will be reduced automatically to a
two bytes value. If the reduced two bytes value is in the valid range,
then it will be accepted and without value exceed limits indication.
Module ID
The diagnostic address of the PROFINET IO device can be treated as the module
ID when read/write record is called. It can be found in the hardware configura-
tion of the software tool.
Fig. 12-125: Diagnostic address
Record Index
The record index corresponds exactly to the function code parameter to be ac-
cessed. The address of the function code parameter is composed of a higher
byte representing the parameter group and a lower byte representing the sub-in-
dex in the group.
The parameter group map is shown as below.
Group
Index
b
0...9
d
0...9
C
0...9
E
0...9
U
0...9
Value
0x00...0x09
0x10...0x19
0x20...0x29
0x30...0x39
0x40...0x49
R912005854_Edition 09 Bosch Rexroth AG
407/653
Functions and Parameters
Example
b0: 0x00
d0: 0x10
C3: 0x23
E8: 0x38
U1: 0x41