58/653
Frequency Converter Wiring
8.2 Cable Specifications
8.2.1 Power Cables
Cable specification for international without USA / Canada
Use copper wires specified for 90 ℃ or above.
●
Insulation based on IEC60364-5-52.
●
Cable with concentric shielding must be used.
●
According to IEC61800-5-1, PE cable must be at least 10 mm
●
double PE cable must be used.
*: If additional labels available with the terminals of 0K40...7K50,
●
please refer to the torque data on labels.
EFC x610
Fuse (gG)
Model
[A]
0K40
10.0
0K75
16.0
1K50
25.0
2K20
32.0
Tab. 8-1: 1P 200 VAC fuse and cable dimensions for international without USA / Canada
①
: Stranded with ferrule without plastic sleeve.
Fuse
EFC x610
(gG)
Model
[A]
0K40
10.0
0K75
10.0
1K50
20.0
Bosch Rexroth AG R912005854_Edition 09
Power cables installation mode
B1
B2
[mm
2
]
2.5
2.5
2.5
2.5
4.0
4.0
6.0
6.0
①
①
Power cables installation mode
B1
B2
[mm
2
]
2.5
2.5
2.5
2.5
4.0
4.0
Rexroth Frequency Converter EFC x610
PE Cable
E
[mm
2
]
10.0
2.5
2.5*2
10.0
2.5
2.5*2
10.0
2.5
4.0*2
10.0
4.0
6.0*2
PE Cable
E
[mm
2
]
10.0
2.5
2.5*2
10.0
2.5
2.5*2
10.0
2.5
4.0*2
Series
2
or a
Torque / Screw
[N·m / lbf·in] (Mx)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
Torque / Screw
[N·m / lbf·in] (Mx)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)
0.8* / 7.0 (M3)