Rexroth Frequency Converter EFC x610
Series
Terminal
Description
B
External brake resistor terminal
(-)
DC negative bus terminal (only available with models of 5K50 and above)
(+)
DC positive bus terminal
Tab. 8-8: 3P 200 / 380 VAC power terminals description
Fig. 8-5: Grounding and PE terminals
1: Grounding terminal for mains cables
2: Reserved for PE / shielding adapter (Order additionally)
3: Reserved for PE / shielding adapter (Order additionally)
4: Grounding terminal for motor cables
Fig. 8-6: Connection screw for internal EMC filter
The connection screw for the internal EMC filter as shown in the figure above is
located at the side of the frequency converter.
Disconnect the internal EMC filter when installing the drive on an
●
IT system (an ungrounded power system or a high-resistance-
grounded [over 30 ohms] power system), otherwise the system
will be connected to ground potential through the EMC filter ca-
pacitors. This may cause danger or damage the drive.
Disconnect the internal EMC filter when installing the drive on a
●
corner-grounded TN system, otherwise the drive will be damaged.
When the internal EMC filter is disconnected, the drive is not EMC
●
compatible.