Rexroth Frequency Converter EFC x610
Series

C2: V/f control parameters

Code
Name
C2.00 V/f curve mode
C2.01 V/f frequency 1
C2.02 V/f voltage 1
C2.03 V/f frequency 2
C2.04 V/f voltage 2
C2.05 V/f frequency 3
C2.06 V/f voltage 3
C2.07 Slip compensation factor
V/f separation output voltage
C2.08
source selection
V/f separation output voltage
C2.09
digital setting
V/f separation output voltage
C2.10
acceleration time
V/f separation output voltage
C2.11
deceleration time
V/f separation stop mode se-
C2.12
lection
C2.13 V/f separation boost factor
C2.20 0 Hz output mode
Setting range
0: Linear
1: Square
2: User-defined
3: V/f separation
0.00...[C2.03] Hz
0.0...120.0 %
[C2.01]...[C2.05] Hz
0.0...120.0 %
[C2.03]...[E0.08] Hz
0.0...120.0 %
0...200 %
0: Panel potentiometer
1: Panel button setting
2: AI1 analog input
10: X5 pulse input
20: Communication (Modbus
0x7F0B/Fieldbus extension
card H0.50)
22: Digital setting
23: Voltage PID control
0.00...100.00 %
0.0...6,000.0 s
0.0...6,000.0 s
0: Voltage and frequency de-
celerates independently
1: Voltage decelerates to zero,
then frequency decelerates to
zero
0.00...100.00
0: No output
1: Standard
R912005854_Edition 09 Bosch Rexroth AG
589/653
Appendix
Default
Min.
Attri.
0
Stop
0.00
0.01
Stop
0.0
0.1
Stop
0.00
0.01
Stop
0.0
0.1
Stop
50.00
0.01
Stop
100.0
0.1
Stop
0
1
Run
22
Stop
0.00
0.01
Run
0.0
0.1
Run
0.0
0.1
Run
0
Run
0.00
0.01
Run
1
1
Stop