Pid Regulation Mode Setting; Pid Feedforward Control - Bosch rexroth EFC 610 Series Operating Instructions Manual

Frequency converter
Hide thumbs Also See for rexroth EFC 610 Series:
Table of Contents

Advertisement

Rexroth Frequency Converter EFC x610
Series

PID Regulation Mode Setting

Parameter [E4.30] 'PID deadband' is used to set the limit of the deviation be-
tween reference and feedback value. When the difference is within the defined
'PID deadband', PID control stops to bring a stable output.
When the PID output reaches [E0.09] 'Output frequency high limit' or
[E0.10]'Output frequency low limit' in PID control, following modes that is de-
fined by Parameter [E4.31] 'PID regulation mode' are available for PID regula-
tion:
[E4.31] = 0: Stop integral regulation when frequency arrives at upper / lower
limit
When the difference between the reference values and the feedback values
changes, the integral value follows immediately the difference. When the setting
frequency reaches the limits, the integration stops, and the integral value re-
mains unchanged. This mode is used in applications with fast change reference
values.
[E4.31] = 1: Continue integral regulation when frequency arrives at upper / low-
er limit
When the PID output reaches the limits, the integral continues up to its possible
numerical limit.
This mode is used in applications with stable reference values. When the differ-
ence between reference and feedback changes, more time is needed to elimi-
nate the impact of accumulated integral regulation before the integral value can
follow the change in the trend.

PID Feedforward Control

PID feedforward controls the process item through amending the output fre-
quency setting with the fine tuning signal of PID output. Before using this func-
tion, users need set [E4.00] ≠ 0, and E4.33 should be set refer to the following
choice:
0: PID feedforward inactive. If [E4.00] ≠ 0, the given frequency is set by PID
output.
1: PID feedforward activate. If [E4.00] ≠ 0, the given frequency is set by the
result of PID output plus the main frequency setting; the given frequency is
set by parameter E0.00 "First frequency setting source", and be obtained
through Acc / Dcc module.