Rexroth Frequency Converter EFC x610
Series
12.9 E1: Input Terminal
12.9.1 Digital Input Configuration
This function defines 5 multi-function digital inputs with PNP and NPN wiring.
Code
Name
E1.00 X1 input
E1.01 X2 input
E1.02 X3 input
E1.03 X4 input
E1.04 X5 input
Setting range of E1.00...E1.04:
0: Inactive
●
No function assigned.
1: Multi-speed control input 1
●
2: Multi-speed control input 2
●
3: Multi-speed control input 3
●
4: Multi-speed control input 4
●
16 multi-speeds are available by combination of 4 terminals, details see
ter 12.11 "E3: Multi-Speed and Simple PLC" on page
10: Acceleration / deceleration time 1 activation
●
11: Acceleration / deceleration time 2 activation
●
12: Acceleration / deceleration time 3 activation
●
Used to switch between 8 groups of acceleration / deceleration time, details
see
chapter 12.11 "E3: Multi-Speed and Simple PLC" on page
15: Freewheeling stop activation
●
'Freewheeling stop activation' generates a stop command and forces the fre-
quency converter to freewheel to stop regardless of the stopping mode con-
figured by E0.50.
16: Stop DC-braking activation
●
This function is used when stopping mode is set with [E0.50] = '0: Decelerat-
ing stop', details see
20: Frequency Up command
●
21: Frequency Down command
●
22: Up / Down command reset
●
Used to change the output frequency, details see
put Frequency Change Function" on page
23: Torque / speed control switch
●
Setting range
0...51
chapter 12.8.9 "Stop Mode Configuration" on page
Functions and Parameters
Default
Unit
35
-
36
-
0
-
0
-
0
-
262.
chapter 12.9.3 "Digital In-
239.
R912005854_Edition 09 Bosch Rexroth AG
229/653
Step
Attri.
-
Stop
-
Stop
-
Stop
-
Stop
-
Stop
chap-
262.
216.