Rexroth Frequency Converter EFC x610
99/653
Series
Electromagnetic Compatibility (EMC)
Point of Connection for Environment Grounding Conductor at Machine, Installa-
tion, Control Cabinet
The equipment grounding conductor of the power cable of the machine, installa-
tion or control cabinet has to be permanently connected at point PE and have a
2
cross section of at least 10 mm
or to be complemented by a second equipment
grounding
conductor
via
separate
terminal
connectors
(according
to
EN 61800-5-1: 2007, section 4.3.5.4). If the cross section of the outer conductor
is bigger, the cross section of the equipment grounding conductor must be ac-
cordingly bigger.
R912005854_Edition 09 Bosch Rexroth AG