208/653
Functions and Parameters

12.8.6 Acceleration and Deceleration Setting

This function defines the configuration of acceleration and deceleration process.
Code
Name
Acceleration / deceleration
E0.25
curve mode
E0.26 Acceleration time
E0.27 Deceleration time
E0.28 S-curve starting phase factor
E0.29 S-curve stopping phase factor
'Acceleration time' is the time for frequency increase from 0.00 Hz to [E0.08]
'Maximum output frequency'.
'Deceleration time' is the time for frequency decrease from [E0.08] 'Maximum
output frequency' to 0.00 Hz.
Fig. 12-55: Acceleration and deceleration time
There are eight groups of acceleration / deceleration time which is selected with
external control terminals. Group E0.26 and E0.27 is used as default value if no
acceleration / deceleration time terminal is defined. For using of other accelera-
tion / deceleration time which is defined by E3.10...E3.23, up to three terminals
of E1.00...E1.04 and H8.00...H8.04 should be selected to '10: Acceleration / de-
celeration time 1 activation', '11: Acceleration / deceleration time 2 activation'
and '12: Acceleration / deceleration time 3 activation'. See
"Simple PLC and Multi-Speed Setting" on page
Two curve modes are available for acceleration / deceleration which is defined
by [E0.25] : 'linear curve' and 'S-curve'.
[E0.25] = 0: Linear mode
Bosch Rexroth AG R912005854_Edition 09
Rexroth Frequency Converter EFC x610
Setting range
Default
0: Linear mode
1: S-curve
0.1...6,000.0 s
DOM
0.1...6,000.0 s
DOM
0.0...40.0 %
20.0
0.0...40.0 %
20.0
262.
Unit
Step
0
-
-
s
0.1
s
0.1
-
0.1
-
0.1
chapter 12.11.1
Series
Attri.
Stop
Run
Run
Stop
Stop