544/653
Accessories

Electric data

Electric data of EMC filter for 1P 200 VAC models
When using EMC filters in mains grounded via outer conductor, use
an isolating transformer between mains and EMC filter.
Description
Degree of protection according to IEC
60529
Listing according to UL standard (UL)
Listing according to CSA standard (UL)
Mass (weight)
Mains voltage at TN-S, TN-C, TT mains
Mains voltage at Corner- grounded-Delta
mains
Mains voltage at IT mains
Tolerance U
(UL)
LN
Input frequency (UL)
Nominal current
Calculation of leakage current
Required wire size according to IEC
60364-5-52; at I
L_cont
Required wire size according to UL 508 A
(internal wiring); at I
L_cont
Tab. 15-16: 1P 200 VAC electric data
Bosch Rexroth AG R912005854_Edition 09
Symbol
I
L_cont
(UL)
Rexroth Frequency Converter EFC x610
0010-
Unit
N-03
m
kg
0.42
U
V
LN
U
V
LN
U
V
LN
f
Hz
LN
A
10
I
mA
< 0.5
leak
A
2
mm
2
LN
A
AWG
14
LN
Series
0020-
0025-
N-03
N-03
IP 20
UL 1283
C22.2 No.8
0.86
0.87
200...240
Not allowed
Not allowed
-10...+10 %
50...60
20
25
< 3.5
< 3.5
3.5
5.3
12
10