Bosch rexroth EFC 610 Series Operating Instructions Manual page 281

Frequency converter
Hide thumbs Also See for rexroth EFC 610 Series:
Table of Contents

Advertisement

Rexroth Frequency Converter EFC x610
Series
See
chapter 12.11 "E3: Multi-Speed and Simple PLC" on page
10: Converter undervoltage
The output is active when DC-bus voltage is lower than 230 VDC (1P 200 VAC
models) / 430 VDC (3P 400 VAC models). The output will be inactive when
DC-bus voltage resumes and becomes stable.
In addition, this digital output will be activated by any soft start error.
11: Converter overload pre-warning
See
chapter 12.2.12 "Converter Overload Pre-Warning" on page
12: Motor overload pre-warning
See
chapter 12.3.6 "Motor Overload Pre-Warning" on page
13: Converter stop by external error
This signal is activated when the error "E.-St" is generated and deactivated
when this error is reset. See
page 229
when digital input is set to '32: Error signal N.O. contact input' and
'33: Error signal N.C. contact input'.
14: Converter error
The output is active when an error occurs, inactive when the error is reset.
15: Converter OK
The output is inactive when the frequency converter is powered off or en-
counters error / warning.
The output is active when the frequency converter is powered on but not run-
ning, or the frequency converter is running without error / warning.
16: Counter target value arrival
17: Counter middle value arrival
See
chapter 12.10.6 "Pulse Counter Function" on page
18: PID reference engineering value arrival
Used for PID function, see
19: Pulse output mode enable
See
chapter 12.10.2 "Pulse Output Setting" on page
20: Torque control mode
The output is active when the frequency converter is in torque control mode.
The output is inactive when the frequency converter is not in torque control
mode.
21: Parameter setting from communication
– For modbus mode, the output is defined by bit0 of register 0x7F08, when
bit0 of register 0x7F08 is '0', open collector is opened; when bit0 of regis-
ter 0x7F08 is '1', open collector is closed.
chapter 12.9.1 "Digital Input Configuration" on
chapter 12.12 "E4: PID Control" on page
R912005854_Edition 09 Bosch Rexroth AG
247/653